Title 26 BUILDING CODE*
CHAPTER 14 EXTERIOR WALLS
SECTION 1403--PERFORMANCE REQUIREMENTS
SECTION 1405--INSTALLATION OF WALL COVERINGS
SECTION 1403--PERFORMANCE REQUIREMENTS
1403.3 Structural. Exterior walls, and the associated openings,
shall be designed and constructed to resist safely the superimposed loads
required by Chapter 16.
In no case shall veneer be considered as part of the
wall in computing strength of deflection nor shall it be considered a part of
the required thickness of the wall. Deflection of lateral support of veneer,
including wood studs, shall be no greater than h/500. (Ord. 2010-0053 § 24,
2010; Ord. 2007-0108 § 4 (part), 2007.)
SECTION 1405--INSTALLATION OF WALL COVERINGS
1405.6 Masonry or Stone veneer. Support of masonry and stone
veneer shall be designed by a registered design professional, unless the masonry
or stone veneer complies with the following: (Ord. 2007-0108 § 4 (part),
2007.)
1405.6.1. Masonry and stone units [5 inches (127 mm) maximum
in thickness]. Masonry and stone veneer not exceeding 5 inches (127 mm) in
thickness may be anchored directly to structural masonry, concrete or studs in
one of the following manners:
1. Wall ties conforming to the following
requirements. Wall ties shall be corrosion resistant, made of sheet metal, shall
have a minimum thickness of .0785 inch (02.00 mm) (No. 14 galvanized sheet gage)
by 1 inch (25.4 mm) and shall be attached to the backing, as the veneer is laid,
by minimum #10 hex head galvanized screws with penetration of at least 2 inches
(51 mm) into the framing member, placed not more than 1/4 inch (6.35 mm) above
the extended leg of the angle tie. Wall ties shall be spaced so as to support
not more than 2 square feet (0.19 m2) of wall area but shall not be more than 24
inches (610 mm) on center horizontally. For Seismic Design Categories D, E,
& F, wall ties shall have a lip or hook on the extended leg that will engage
or enclose a horizontal joint reinforcement wire having a diameter of 0.148 inch
(3.76 mm) (No. 9 B.W. gage) or equivalent. The joint reinforcement shall be
continuous with butt splices between ties permitted.
When applied over wood
stud construction, the studs shall be spaced a maximum of 16 inches (406 mm) on
center and approved paper, a minimum 30# fiberglass felt, 4 inch (102 mm)
minimum on horizontal laps and 6 inch (152 mm) minimum on end laps, shall first
be applied over minimum 15/32 inch (12 mm) plywood sheathing except as otherwise
provided in Section 91.1402, and an air space of at least 1-inch (25 mm) shall
be maintained between the backing and the veneer. Spot bedding at all ties shall
be of cement mortar.
2. Veneer conforming to the following requirements:
Veneer applied with 1-inch-minimum (25 mm) grouted backing space which is
reinforced by not less than 2-inch by 2-inch (51 mm by 51 mm) 0.065 inch (1.65
mm) (No. 16 B.W. gage) galvanized wire mesh placed over waterproof paper backing
and anchored directly to stud construction. Such construction shall be allowed
to a height not to exceed 4 feet (1219 mm) above grade.
The stud spacing
shall not exceed 16 inches (406 mm) on center. The galvanized wire mesh shall be
anchored to wood studs by galvanized steel wire furring nails at 4 inches (102
mm) on center or by barbed galvanized nails at 6 inches (152 mm) on center with
a 11/8-inch-minimum (29 mm) penetration. The galvanized wire mesh may be
attached to steel studs by equivalent wire ties. If this method is applied over
solid sheathing the mesh must be furred for embedment in grout. The wire mesh
must be attached at the top and bottom with not less than 8d (64 mm) common wire
nails. The grout fill shall be placed to fill the space intimately around the
mesh and veneer facing. (Ord. 2007-0108 § 4 (part),
2007.)
1405.6.2. Stone units [10 inches (254 mm) maximum in
thickness]. Stone veneer units not exceeding 10 inches (254 mm) in thickness
may be anchored directly to structural masonry or concrete. Anchor ties shall
not be less than 0.109 inch (2.77 mm) (No. 12 B.W. gage) galvanized wire, or
approved equal, formed as an exposed eye and extending not less than 1/2 inch (3
mm) beyond the face of the backing. The legs of the loops shall not be less than
6 inches (152 mm) in length bent at right angles and laid in the masonry mortar
joint and spaced so that the eyes or loops are 12 inches (254 mm) maximum on
center in both directions. There shall be provided not less than a 0.109 inch
(2.77 mm) (No. 12 B.W. gage) galvanized wire tie, or approved equal, threaded
through the exposed loops for every 2 square feet (0.19 m2) of stone
veneer. This tie shall be a loop having legs not less than 15 inches (381 mm) in
length so bent that it will lie in the stone veneer mortar joint. The last 2
inches (51 mm) of each wire leg shall have a right angle bend. One inch (25 mm)
of cement grout shall be placed between the backing and the stone veneer. (Ord.
2007-0108 § 4 (part), 2007.)
<< previous | next >>