Title 26 BUILDING CODE*
CHAPTER 19 CONCRETE
SECTION 1908--MODIFICATIONS TO ACI 318
SECTION 1909 STRUCTURAL PLAIN CONCRETE
SECTION 1908--MODIFICATIONS TO ACI 318
1908.1 General. The text of ACI 318 shall be modified as
indicated in Sections 1908.1.1 through 1908.1.14. (Ord. 2010-0053 § 45,
2010.)
1908.1.2 ACI 318, Section 21.1.1.
Modify ACI 318,
Sections 21.1.1.3, and 21.1.1.7 as follows:
. . .
All special moment
frames and special structural walls shall also satisfy 21.1.3 through 21.1.7.
Concrete tilt-up wall panels classified as intermediate precast structural wall
systems shall satisfy 21.9 in addition to 21.4.2 and 21.4.3 for structures
assigned to Seismic Design Category D, E, or F. (Ord. 2010-0053 § 46,
2010.)
1908.1.3 ACI 318, Section 21.4.
Modify ACI 318,
Section 21.4, by renumbering Section 21.4.3 to become 21.4.4 and adding new
Sections 21.4.3, 21.4.5, 21.4.6, and 21.4.7 to read as follows:
. . .
21.4.5 -- [BSC] Wall piers in Seismic Design Category D, E, or F shall
comply with Section 1908.1.4 of this Code. The requirement shall be applicable
to all buildings.
. . .
(Ord. 2010-0053 § 47,
2010.)
1908.1.8 ACI 318, Section 22.10.
Delete ACI 318,
Section 22.10, and replace with the following:
. . .
22.10.1 --
Structures assigned to Seismic Design Category C, D, E, or F shall not have
elements of structural plain concrete, except as follows:
(a) Concrete used
for fill with a minimum cement content of two (2) sacks of Portland cement per
cubic yard.
(b) Isolated footings of plain concrete supporting pedestals or
columns are permitted, provided the projection of the footing beyond the face of
the supported member does not exceed the footing thickness.
(c) Plain
concrete footings supporting walls are permitted, provided the footings have at
least two continuous longitudinal reinforcing bars. Bars shall not be smaller
than No. 4 and shall have a total area of not less than 0.002 times the gross
cross-sectional area of the footing. A minimum of one bar shall be provided at
the top and bottom of the footing. Continuity of reinforcement shall be provided
at corners and intersections.
In detached one- and two-family dwellings
three stories or less in height and constructed with stud-bearing walls, plain
concrete footings with at least two continuous longitudinal reinforcing bars not
smaller than No. 4 are permitted to have a total area of less than 0.002 times
the gross cross-sectional area of the footing. (Ord. 2010-0053 § 48,
2010.)
1908.1.11 ACI 318, Section 21.6.4.1. Modify ACI 318,
Section 21.6.4.1, to read as follows:
Where the calculated point of
contraflexure is not within the middle half of the member clear height, provide
transverse reinforcement as specified in ACI 318, Sections 21.6.4.1, Items (a)
through (c), over the full height of the member. (Ord. 2010-0053 § 49,
2010.)
1908.1.12 ACI 318, Section 21.6.4. Modify ACI 318,
Section 21.6.4, by adding Section 21.6.4.8 to read as follows:
21.6.4.8 --
At any section where the design strength, φPn, of the column is
less than the sum of the shears Ve computed in accordance with ACI
318 Sections 21.5.4.1 and 21.6.5.1 for all the beams framing into the column
above the level under consideration, transverse reinforcement as specified in
ACI 318 Sections 21.6.4.1 through 21.6.4.3 shall be provided. For beams framing
into opposite sides of the column, the moment components may be assumed to be of
opposite sign. For the determination of the design strength, φPn, of the
column, these moments may be assumed to result from the deformation of the frame
in any one principal axis. (Ord. 2010-0053 § 50,
2010.)
1908.1.13 ACI 318, Section 21.9.4. Modify ACI 318, Section
21.9.4, by adding Section 21.9.4.6 to read as follows:
21.9.4.6 -- Walls and
portions of walls with Pu > 0.35Po shall not be
considered to contribute to the calculated strength of the structure for
resisting earthquake-induced forces. Such walls shall conform to the
requirements of ACI 318 Section 21.13. (Ord. 2010-0053 § 51,
2010.)
1908.1.14 ACI 318, Section 21.11.6. Modify ACI 318,
Section 21.11.6, by adding the following:
Collector and boundary elements in
topping slabs placed over precast floor and roof elements shall not be less than
3 inches (76 mm) or 6 db thick, where db is the diameter of the largest
reinforcement in the topping slab. (Ord. 2010-0053 § 52,
2010.)
1908.1.15 ACI 318, Section 22.10. Delete ACI 318, Section
22.10, and replace with the following:
22.10 -- Plain concrete in structures
assigned to Seismic Design Category C, D, E or F.
22.10.1 -- Structures
assigned to Seismic Design Category C, D, E or F shall not have elements of
structural plain concrete, except as follows:
(a) Concrete used for fill
with a minimum cement content of two (2) sacks of Portland cement per cubic
yard.
(b) Isolated footings of plain concrete supporting pedestals or
columns are permitted, provided the projection of the footing beyond the face of
the supported member does not exceed the footing thickness.
(c) Plain
concrete footings supporting walls are permitted provided the footings have at
least two continuous longitudinal reinforcing bars. Bars shall not be smaller
than No. 4 and shall have a total area of not less than 0.002 times the gross
cross-sectional area of the footing. A minimum of one bar shall be provided at
the top and bottom of the footing. Continuity of reinforcement shall be provided
at corners and intersections.
In detached one- and two-family dwellings
three stories or less in height and constructed with stud-bearing walls, plain
concrete footings with at least two continuous longitudinal reinforcing bars not
smaller than No. 4 are permitted to have a total area of less than 0.002 times
the gross cross-sectional area of the footing. (Ord. 2007-0108 § 13 (part),
2007.)
1908.1.17 ACI 318, Section 14.8. Modify ACI 318 Section
14.8.3 and 14.8.4 replacing equation (14-7), (14-8) and (14-9) as
follows.
1. Modify equation (14-7) of ACI 318 Section 14.8.3 as
follows:
I cr shall be calculated by Equation (14-7), and
Ma shall be obtained by iteration of deflections.

and
the value E
s/E
c shall not be taken less than
6.
2. Modify ACI 318 Sec, 14.8.4 as follows:
14.8.4 --
Maximum out-of-plane deflection, Δ
s, due to service loads,
including PΔ effects, shall not exceed l
c/150.
If
M
a, maximum moment at mid-height of wall due to service lateral and
eccentric loads, including PΔ effects, exceed (2/3) M
cr,
Δ
s shall be calculated by Equation
(14-8):
TITLE2608.jpg (14-8)
If M
a does not
exceed (2/3) M
cr, Δ
s shall be calculated by Equation
(14-9):
TITLE2609.jpg (14-9)
where:

(Ord. 2007-0108 § 13 (part),
2007.)
1908.1.18 ACI 318, Section 21.4.4.1. Modify ACI 318
Section 21.4.4.1 as follows:
Where the calculated point of
contra-flexure is not within the middle half of the member clear height, provide
transverse reinforcement as specified in ACI 318 Sections 21.4.4.1, Items (a)
through (c), over the full height of the member. (Ord. 2007-0108 § 13
(part), 2007.)
1908.1.19 ACI 318, Section 21.4.4. Modify ACI 318
by adding Section 21.4.4.7 as follows:
21.4.4.7 -- At any section
where the design strength, φP
n, of the column is less than the
sum of the shears V
e computed in accordance with ACI 318 Sections
21.3.4.1 and 21.4.5.1 for all the beams framing into the column above the level
under consideration, transverse reinforcement as specified in ACI 318 Sections
21.4.4.1 through 21.4.4.3 shall be provided. For beams framing into opposite
sides of the column, the moment components may be assumed to be of opposite
sign. For the determination of the design strength, φP
n, of the
column, these moments may be assumed to result from the deformation of the frame
in any one principal axis. (Ord. 2007-0108 § 13 (part),
2007.)
1908.1.20 ACI 318, Section 21.7.4. Modify ACI 318 by
adding Section 21.7.4.6 as follows:
21.7.4.6 -- Walls and
portions of walls with P
u > 0.35P
o shall not be
considered to contribute to the calculated strength of the structure for
resisting earthquake-induced forces. Such walls shall conform to the
requirements of Section 1631.2, Item 4 ACI 318 Section 21.11. (Ord. 2007-0108
§ 13 (part), 2007.)
1908.1.21 ACI 318, Section 21.9.4.
Modify ACI 318 section 21.9.4 by adding the following:
Collector and
boundary elements in topping slabs placed over precast floor and roof elements
shall not be less than 3 inches (76 mm) or 6 d
b thick, where
d
b is the diameter of the largest reinforcement in the topping slab.
(Ord. 2007-0108 § 13 (part), 2007.)
SECTION 1909 STRUCTURAL PLAIN CONCRETE
1909.4 Design.
. . .
Exception: For Group
R-3 occupancies and buildings or other occupancies less than two stories above
grade plane of light-frame construction, the required edge thickness of ACI 318
is permitted to be reduced to 6 inches (152 mm), provided that the footing does
not extend more than 4 inches (102 mm) on either side of the supported wall.
This exception shall not apply to structural elements designed to resist seismic
lateral forces for structures assigned to Seismic Design Category D, E, or
F.
(Ord. 2010-0053 § 53, 2010.)