Title 26 BUILDING CODE*
CHAPTER 95 EARTHQUAKE HAZARD REDUCTION FOR EXISTING CONCRETE TILT-UP BUILDINGS
SECTION 9501--PURPOSE
SECTION 9502--SCOPE
SECTION 9503--DEFINITIONS
SECTION 9504--ADMINISTRATION
SECTION 9505--GENERAL REQUIREMENTS
SECTION 9506--ANALYSIS AND DESIGN
SECTION 9507--MATERIALS OF CONSTRUCTION
SECTION 9508--PLANS
align="center">TABLE 95-ATIME LIMITS FOR COMPLIANCE WITH EARTHQUAKE HAZARD REDUCTION COMPLIANCE ORDER1,2
Title 26 of the Los Angeles County Code is amended by adding Chapter 95,
entitled “EARTHQUAKE HAZARD REDUCTION FOR EXISTING CONCRETE TILT-UP
BUILDINGS,” to read as follows:
SECTION 9501--PURPOSE
The purpose of this Chapter is to promote public safety and welfare by
reducing the risk of death or injury which might otherwise result from
earthquake damage to concrete tilt-up buildings constructed, under construction,
or for which a building permit was issued prior to April 13, 1975. Such
buildings have been widely recognized as having a potentially significant risk
of sustaining life-hazardous damage, including partial or complete collapse
during moderate to strong earthquakes, due to inadequate wall anchorage to the
horizontal diaphragm.
This Chapter provides systematic procedures and
standards for identification of such concrete tilt-up wall buildings, and time
periods under which these buildings are required to be structurally analyzed and
anchored. Where analysis finds deficiencies, this Chapter requires the building
to be strengthened or demolished.
This Chapter sets forth minimum standards
for structural seismic resistance to reduce the risk of loss of life and injury
by the installation of wall anchors and connections to the horizontal
diaphragms. Compliance with these standards will not necessarily prevent loss of
life or injury, or prevent earthquake damage to rehabilitated buildings. This
Chapter does not require existing electrical, plumbing, mechanical or firesafety
systems to be altered. (Ord. 99-0040 § 74 (part), 1999.)
SECTION 9502--SCOPE
The provisions of this Chapter shall apply to all buildings
constructed, under construction, or for which a building permit was issued prior
to April 13, 1975, and which on the effective date of this ordinance have
concrete tilt-up bearing walls as defined herein. (Ord. 2007-0108 § 30
(part), 2007: Ord. 99-0040 § 74 (part), 1999.)
SECTION 9503--DEFINITIONS
For purposes of this Chapter, the applicable definitions in Chapter 16
of this Code and the following definitions shall apply.
ESSENTIAL
FACILITIES is defined as any building conforming to the definition of
essential facilities as set forth in Section 1602.1 of this Code.
TILT-UP CONCRETE WALL is a form of precast concrete panel
construction, where the panel is either cast at the construction site in a
horizontal position, or offsite and, after curing, incorporated into the
structure of the building, in a vertical position. (Ord. 2007-0108 § 30
(part), 2007; Ord. 2002-0076 § 146, 2002: Ord. 99-0040 § 74 (part),
1999.)
SECTION 9504--ADMINISTRATION
9504.1 Service of Order. The Department of Public Works shall
attempt to identify those buildings within the scope of this Chapter and shall
take reasonable measures to issue an Earthquake Hazard Reduction Compliance
Order as provided in this Section. (Ord. 99-0040 § 74 (part), 1999.)
9504.2 Contents of Order. The Earthquake Hazard Reduction
Compliance Order shall be in writing and shall be served either personally or by
mail, postage prepaid, upon the owner as shown on the last equalized assessment,
or by posting on the building. The order shall specify that the building appears
to be within the scope of this Chapter and, therefore, is required to meet the
minimum seismic standards of this Chapter. The order shall also specify the time
limits for appeal of and compliance with the order. (Ord. 2002-0076 § 147,
2002: Ord. 99-0040 § 74 (part), 1999.)
9504.3 Appeal from Order. The owner may appeal the Building
Official’s initial determination that the building is within the scope of
this Chapter to the Building Board of Appeals established by Section 105. Such
appeal shall be filed with the Board within 60 days from the service date of the
order described in Section 9504.2. Any such appeal shall be heard by the Board
no later than 90 days after the date that the appeal is filed. Such appeal shall
be made in writing and the grounds thereof shall be stated clearly and
concisely. All materials which the appellant wishes considered by the Building
Board of Appeals shall be submitted to the Board 14 calendar days before the
hearing.
Appeals and requests for modifications from any other
determinations, orders or actions of the Department of Public Works pursuant to
this Chapter shall be made in accordance with the normal appeal procedures
established in Sections 104.2.7 and 105. (Ord. 2002-0076 § 148, 2002: Ord.
99-0040 § 74 (part), 1999.)
9504.4 Recordation. At or about the time that the Earthquake
Hazard Reduction Compliance Order is served, the Department of Public Works
shall file with the Office of the County Recorder a certificate stating that the
subject building appears to be within the scope of Chapter 95. The certificate
shall state that the owner thereof has been ordered to structurally analyze the
building and, if necessary, to structurally alter or demolish the building as
set forth in Chapter 95. The certificate shall also state that the owner has 60
days from the date of the order to appeal the determination that the subject
building is within the scope of Chapter 95 and that if such an appeal is not
submitted, the determination will be final and binding.
If the building is
subsequently determined by the Department of Public Works not to be within the
scope of this Chapter, or is demolished, or is modified so as to meet the
requirements of this Chapter, the Department of Public Works shall file with the
Office of the County Recorder a certificate terminating the status of the
subject building as being classified within the scope of Chapter 95. (Ord.
2002-0076 § 149, 2002; Ord. 99-0040 § 74 (part), 1999.)
9504.5 Enforcement. If the owner of the subject building fails
to comply with any order issued by the Department of Public Works pursuant to
this Chapter, the Department of Public Works may order the entire building
vacated and maintained vacated until such compliance has been accomplished. If,
within 90 days after the date the building has been ordered vacated, or within
such additional time as may have been granted by the Building Board of Appeals,
the owner or other person in charge or control of the subject building has still
not complied with any order issued pursuant to this Chapter, the Department of
Public Works may order demolition of the building in accordance with the
provisions of Section 102 of this Code. (Ord. 2002-0076 § 150, 2002: Ord.
99-0040 § 74 (part), 1999.)
9504.6 Prosecution. In case the owner shall fail, neglect or
refuse to comply with the directions in the Earthquake Hazard Reduction
Compliance Order (if neither the owner nor any other person requests a hearing)
or with any order of the Building Board of Appeals, the owner shall be guilty of
a misdemeanor and the building official may cause such owner of the building or
property to be prosecuted as a violator of this Code. (Ord. 2002-0076 § 151
(part), 2002.)
9504.7 Other Abatement Procedures. The provisions of this
Chapter shall not in any manner limit or restrict the County or the District
Attorney from enforcing County Ordinances or abating public nuisances in any
other manner provided by law. (Ord. 2002-0076 § 151 (part), 2002.)
SECTION 9505--GENERAL REQUIREMENTS
The owner of each building within the scope of this Chapter shall,
upon service of an Earthquake Hazard Reduction Compliance Order, cause a
structural analysis of the building to be made by a civil or structural engineer
or architect licensed by the State of California to conduct structural analysis
and shall submit such analysis to the Department of Public Works for review. The
structural analysis shall state whether or not the building meets the
requirements of this Chapter. If such a structural analysis indicates that the
building does not meet the requirements of this Chapter, the owner shall either
obtain a demolition permit and demolish the building or submit plans for
structural alterations of the building so that it will comply with the
provisions of this Chapter together with a structural analysis so indicating,
and perform the work.
The owner shall submit the required structural
analysis, obtain any necessary permits and commence and complete the required
alteration or demolition within the time limits set forth in Table 95-A. These
time limits shall run from the date the Earthquake Hazard Reduction Compliance
Order is served.
Once an Earthquake Hazard Reduction Compliance Order has
been served, buildings within the scope of this Chapter may not be structurally
altered, remodeled or added to without first complying with the provisions of
this Chapter unless the Building Official determines that the alteration is
minor in nature. (Ord. 2002-0076 § 152, 2002: Ord. 99-0040 § 74
(part), 1999.)
SECTION 9506--ANALYSIS AND DESIGN
9506.1 Wall Panel Anchorage. Concrete walls shall be anchored
to all floors and roofs which provide lateral support for the wall. The
anchorage shall provide a positive direct connection between the wall and floor
or roof construction capable of resisting a horizontal force equal to 45 percent
of the tributary wall weight for essential facilities, and 30 percent of the
tributary wall weight for all other buildings, or a minimum force of 250 pounds
per linear foot (3.65 kN/m) of wall, whichever is greater. The required
anchorage shall be based on the tributary wall panel assuming simple supports at
floors and roof. (Ord. 2007-0108 § 30 (part), 2007: Ord. 99-0040 § 74
(part), 1999.)
9506.2 Special Requirements for Wall Anchors and Continuity Ties.
The steel elements of the wall anchorage systems and continuity ties shall
be designed by the allowable stress design method using a load factor of 1.7.
The one-third stress increase permitted by Section 1605.3.2 shall not be
permitted for materials using allowable stress design methods.
The strength
design specified in Section 1912, using a load factor of 2.0 in lieu of 1.4 for
earthquake loading, shall be used for design of embedments in concrete.
Wall
anchors shall be provided to resist out-of-plane forces, independent of existing
shear anchors.
EXCEPTION: Existing cast-in-place shear anchors may be used as wall
anchors if the tie element can be readily attached to the anchors and if the
engineer or architect can establish tension values for the existing anchors
through the use of approved as-built plans or testing, and thorough analysis
showing that the bolts are capable of resisting the total shear load while being
acted upon by the maximum tension force due to earthquake. Criteria for analysis
and testing shall be determined by the Building Official.
Expansion
anchors are not allowed without specific approval of the Building Official.
Attaching the edge of steel decks or plywood sheathing to steel ledgers does not
comply with the positive anchoring requirements of the Code. (Ord. 2007-0108
§ 30 (part), 2007; Ord. 99-0040 § 74 (part), 1999.)
9506.3 Development of Anchor Loads into the Diaphragm.
Development of anchor loads into roof and floor diaphragms shall comply with
Section 9506.10 of this Code.
EXCEPTION: If continuously tied girders are present, then the
maximum allowable spacing between the continuity ties is 36 feet (10 973
mm).
In wood diaphragms, anchorage shall not be accomplished by use of
toenails or nails subject to withdrawal, nor shall wood ledgers, top plates, or
framing be used in cross-grain bending or cross-grain tension. The continuous
ties required by Section 9506.10 shall be in addition to the diaphragm
sheathing.
Lengths of development of anchor loads in wood diaphragms shall
be based on existing field nailing of the sheathing unless existing edge nailing
is positively identified on the original construction plans or at the
site.
At re-entrant corners, continuity collectors may be required for
existing return walls not designed as shear walls, to develop into the diaphragm
a force equal to the lesser of the rocking or shear capacity of the return wall,
or the tributary shear, but not exceeding the capacity of the diaphragm. Shear
anchors for the return wall shall be commensurate with the collector force. If a
truss or beam other than rafters or purlins is supported by the return wall or
by a column integral with the return wall, an independent secondary column is
required to support the roof or floor members.
Seismic design of return
walls and fins/canopies at entrances shall ensure deflection compatibility with
the diaphragm by either seismically isolating the element or attaching the
element and integrating its load into the diaphragm. (Ord. 2010-0053 § 81,
2010; Ord. 99-0040 § 74 (part), 1999.)
9506.4 Anchorage at Pilasters. Anchorage of pilasters shall be
designed for the tributary wall anchoring load per Section 9506.1 of this Code,
considering the wall as a two-way slab. The pilasters or the walls immediately
adjacent to the pilasters shall be anchored directly to the roof framing such
that the existing vertical anchor bolts at the top of the pilasters are
by-passed without causing tension or shear failure at the top of the
pilasters.
EXCEPTION: If existing vertical anchor bolts at the top of the
pilasters are used for the anchorage, then additional exterior confinement shall
be provided.
The minimum anchorage at a floor or roof between the pilasters shall
be that specified in Section 9506.1 of this Code. (Ord. 99-0040 § 74
(part), 1999.)
9506.5 Evaluation of Existing Structural Conditions. If the
structural analysis submitted pursuant to Section 9505 indicates that the
building does not meet the requirements of this Chapter, the engineer or
architect shall include in said analysis a report of any observed structural
conditions, including, but not limited to, cracks, structural damage or
alterations, that may have a substantial effect on the seismic integrity of the
building and shall include provisions for the repair of these conditions in the
plans submitted to the department for review and approval. (Ord. 99-0040 §
74 (part), 1999.)
9506.6 Miscellaneous. Existing mezzanines relying on the
tilt-up walls for vertical and/or lateral support shall be anchored to the walls
for the tributary mezzanine load. Walls depending on the mezzanine for lateral
support shall be anchored per Sections 9506.1, 9506.2 and 9506.3.
EXCEPTION: Existing mezzanines that have independent lateral and
vertical support need not be anchored to the walls.
Existing interior masonry or concrete walls, not designed as shear
walls, which extend to the floor above or to the roof diaphragm shall also be
anchored for out-of-plane forces per Sections 9506.1, 9506.2 and 9506.3 of this
Code. In the in-plane direction, the walls shall be isolated or developed into
the diaphragm to resist a lateral force equal to the lesser of the rocking or
shear capacity of the wall, or the tributary shear, but in no event to exceed
the diaphragm capacity. (Ord. 2002-0076 § 153, 2002: Ord. 99-0040 § 74
(part), 1999.)
9506.7 Symmetry. Symmetry of anchorage systems is required.
Non-symmetrical anchorage systems may be allowed when it can be shown that all
components of forces are positively resisted as determined by calculations or
tests. (Ord. 99-0040 § 74 (part), 1999.)
9506.8 Minimum Roof Member Size. Wood members used to develop
anchorage forces to the diaphragm shall not be less than 3-inch (76mm) nominal
thickness when damaged members are replaced. All such members must be checked
for earthquake loads as part of the wall anchorage system in addition to dead
and live loads. For existing buildings, the member check shall be without the
one-third stress increase per Section 1605.3.2. (Ord. 2007-0108 § 30
(part), 2007: Ord. 99-0040 § 74 (part), 1999.)
9506.9 Combination of Anchor Types. The maximum allowable
combined load resisted by a combination of different types of anchors that
exhibit different behavior or stiffness is not the sum of the allowable load for
each anchor. The combined capacity of the new and existing connectors shall be
taken as the allowable load of the stiffest anchor.
EXCEPTION: Existing anchors may be combined with new anchors for
retrofit projects where existing anchors are undamaged and will resist loads
equally with a new anchor of identical manufacture, type and installation. The
combined allowable load shall be twice the allowable load of a single
anchor.
(Ord. 99-0040 § 74 (part), 1999.)
9506.10 Diaphragms.
Diaphragms supporting concrete walls shall have continuous ties or struts
between diaphragm chords to distribute the anchorage forces specified in Section
12.11 of ASCE 7. The spacing of continuous ties shall not exceed 25 feet (7620
mm). Added chords of subdiaphragms may be used to form subdiaphragms to transmit
the anchorage forces to the main continuous crossties. The maximum diaphragm
shear used to determine the depth of the subdiaphragms shall not exceed 300
pounds per foot (4.38 kN/m). The maximum length-to-width ratio of the wood
structural subdiaphragm shall be 2 ½:1. (Ord. 2010-0053 § 82,
2010.)
SECTION 9507--MATERIALS OF CONSTRUCTION
All materials permitted by this Code may be utilized to meet the
requirements of this Chapter. (Ord. 99-0040 § 74 (part), 1999.)
SECTION 9508--PLANS
9508.1 General. Plans submitted pursuant to the provisions of
this Chapter shall be signed by the licensed civil or structural engineer or
architect responsible for the seismic analysis of the building and shall comply
with the requirements of this Code and this Section. (Ord. 99-0040 § 74
(part), 1999.)
9508.2 Plans and Specifications. Plans, engineering
calculations, diagrams and other data shall be submitted in two or more sets
with each application for a building permit. (Ord. 99-0040 § 74 (part),
1999.)
9508.3 Information on Plans and Specifications. Plans and
specifications shall be drawn to scale upon substantial medium and shall be of
sufficient clarity to indicate the location, nature and extent of the work
proposed and show in detail that the proposed work will conform to the
provisions of this Chapter and all relevant Codes, laws, ordinances, rules and
regulations. (Ord. 99-0040 § 74 (part), 1999.)
9508.4 Existing Construction. The following information shall
be made part of the approved plans:
1. The type and dimensions of existing
walls and the size and spacing of existing floor and roof members.
2. The
extent and type of existing wall anchorage of floors and roof
members.
3. Accurately dimensioned plans and/or elevations of existing
floors and concrete walls showing dimensioned openings, piers, wall thicknesses
and heights.
4. The location and extent of any structural conditions as
specified in Section 9506.5. (Ord. 99-0040 § 74 (part), 1999.)
align="center">TABLE 95-ATIME LIMITS FOR COMPLIANCE WITH EARTHQUAKE HAZARD REDUCTION COMPLIANCE ORDER1,2
|
SUBMIT PLANS WITHIN
|
OBTAIN PERMIT WITHIN
|
COMMENCE ALTERATION OR DEMOLITION WITHIN
|
COMPLETE ALTERATION OR DEMOLITION WITHIN
|
|
12 months
|
18 months
|
24 months
|
36 months
|
1 All dates are measured from the date the Earthquake Hazard
Reduction Compliance Order is served pursuant to Section 9504.
2 For any work required by this Chapter, the time limits shown
herein shall supersede the time limits specified in Section 106.5.4.
(Ord. 2002-0076 § 154, 2002: Ord. 99-0040 § 74 (part),
1999.)
<< previous | next >>